title: 09-02 - CPM Installation
slug: 09-02-cpm-installation
createdAt: 2023-10-08T08:09:09.328Z
---

## &#x20;1. Install Windows&#x20;

## &#x20;2. Setup Username, Password, Computer Name

- Username : CPM-USER
- Password : cpm123
- Computer Name: CSCS-CPM

## &#x20;3. Setup IP Address ตาม System Diagram (Topology) พร้อม Rename Port Ethernet (LAN) เป็น LAN1\_CSCS และ LAN2\_SCADA

&#x20;           For Example:&#x20;

![](https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/mTtFFZ6mFHui22EIosTJJ_image.png)

## &#x20;4. Disable Firewall

- ไปที่ Control Panel > Windows Defender Firewall&#x20;

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/nOIiAZawfZv8x4KUIXVLw_image.png" size="60" width="940" height="736" position="center" darkWidth="940" darkHeight="736" showCaption="false"}

***

- Advanced setting

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/ijWAJ1IUTjmmVLZlsLkLg_image.png" size="66" width="886" height="736" position="center" darkWidth="886" darkHeight="736" showCaption="false"}

- Windows Defender Firewall Properties

![](https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/rZ8sBeynxAMZFgaQsj4h4_image.png)

- เปลี่ยน Firewall State เป็น "Off" ทั้ง Domain Profile, Private Profile, Public Profile

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/odDKY7A4ttBiH5ChRRucH_image.png" size="46" width="497" height="563" position="center" darkWidth="497" darkHeight="563" showCaption="false"}

## &#x20;5. Setup Power and Sleep

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/R2SD6WliaGohkA8loLrMr_image.png" size="60" width="822" height="800" position="center" darkWidth="822" darkHeight="800" showCaption="false"}

## &#x20;6. Enable Remote Desktop Setting

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/AXIRsoG9it_tv2GcymJok_image.png" size="60" width="637" height="478" position="center" darkWidth="637" darkHeight="478" showCaption="false"}

- Uncheck ที่ Require devices to use Network Level Authentication to connect (Recommended)
- สำหรับขั้นตอนนี้จะต้องตั้ง password ของ user account สำหรับ windows ให้เรียบร้อยด้วย หากไม่มี password จะไม่สามารถใช้งาน remote desktop ได้

## &#x20;7. Set Region เป็น English (United Kingdom)

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/s7WA3w2o0cfL_Mn95zitN_image.png" size="62" width="709" height="688" position="center" darkWidth="709" darkHeight="688" showCaption="false"}

## &#x20;8. Install Sentinel HASP Driver และ Connect USB Dongle เข้าที่เครื่อง

## &#x20;9. Install Tardis2000

- Setup Tardis 2000 โดย Software จะอยู่ที่ C:/Windows/SysWOW64/Tardis.cpl

&#x20;                    Note: Run as Administrator

- Disable the windows Time Service (ถ้ามีหน้าต่างถาม)

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/UQqeLwx75gweq4-LtrLMP_image.png" size="56" width="606" height="347" position="center" darkWidth="606" darkHeight="347" showCaption="false"}

- กด Clear All (In Main menu)

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/RXoqYmpiczBOAnbDNEy0k_image.png" size="48" width="393" height="350" position="center" darkWidth="393" darkHeight="350" showCaption="false"}

- กด Add แล้วใส่ IP Address ของ GPS พร้อมระบุชื่อ GPS

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/-7v-l54lC8S_SBGAk2aGn_image.png" size="50" width="599" height="692" position="center" darkWidth="599" darkHeight="692" showCaption="false"}

- ปรับ Parameter ใน "Setting the time" Menu ตามรูป

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/Dge0HThh-7ODp_rcPUvej_image.png" size="46" width="396" height="358" position="center" darkWidth="396" darkHeight="358" showCaption="false"}

- กด "Apply" แล้ว "OK"



## &#x20;10. Install Dotnet Framework 3.5 SP1

## &#x20;11. สร้าง folder CSCS\_Prj ที่ C:/ Drive

::Image[ 9. สร้าง Folder CSCS\_Prj ใน C:/ Drive]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/M7C8X8dY9GocWF_9fQe-M_image.png" size="60" width="1042" height="831" position="center" darkWidth="1042" darkHeight="831" showCaption="false"}

## 12. Copy Backup Configuration จากเครื่องเดิมมาใส่ใน Folder CSCS\_Prj ที่สร้างขึ้นมา

## 13. Create Shortcut iControl.exe

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/IwFe-dAOAiFDnxonPNI8k_image.png" size="70" width="1042" height="831" position="center" darkWidth="1042" darkHeight="831" showCaption="false"}

## 14. ย้าย Shortcut ไปไว้บน Desktop พร้อมกับ rename ชื่อ

## 15. Run iControl Software

## 16. Share Folder C:/CSCS\_Prj/logs/cscs\_prj&#x20;

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/PNlDQHTtYq2QkbFemxx1G_image.png" size="70" width="1042" height="831" position="center" darkWidth="1042" darkHeight="831" showCaption="false"}

## 17. Setup Auto Login สำหรับ Windows ตาม Link

&#x20;      [https://www.stellarinfo.com/article/windows-11-auto-login.php](https://www.stellarinfo.com/article/windows-11-auto-login.php)

## 18. Setup Auto start iControl software (at Startup)

- search run ใน windows or start โดยใช้ key Windows บน keyboard
- open shell\:startup

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/u6pTle67rfMiIMTUut9pt_image.png" size="60" width="456" height="271" position="center" darkWidth="456" darkHeight="271" showCaption="false"}

- Create iControl.exe shortcut อีกครั้ง แล้ว copy ไปใส่ใน folder

::Image[]{src="https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/4OswOR64w4dWKT8Z0JhDm_image.png" size="60" width="1006" height="831" position="center" darkWidth="1006" darkHeight="831" showCaption="false"}

## 19. Install AutoDelete.exe&#x20;

- run AutoDelete.exe
- หลังจากติดตั้งเรียบร้อยจะมี folder AutoDelete ขึ้นใน Drive C:/

## 20. Setup AutoDelete

- เปิด File Setting.config ด้วย Notepad (C:/AutoDelete/Setting/Setting.Config)
- Setting path ของ logs file ให้ถูกต้อง พร้อมทั้งระบุจำนวนวันที่ต้องการเก็บ logs ไว้ก่อน AutoDelete จะลบทิ้ง
- Save ทับ file เดิม

![](https://api.archbee.com/api/optimize/tFXfhzvV83pm_CfOOnnzT/Dk4raanRRqKXz5juRYFGf_image.png)