FRTU/FDCU Support
FTU-F80 Version4(FRTU/FDCU)

FTU-F80(V4) User Manual

95min

1. F80 Series

1.1 F80 General Description

Protocol Support

• DNP3.0 Level 3 Serial (Slave)- with secure authentication implemented • DNP3.0 over TCP/IP (Slave) with secure authentication implemented. • IEC 61850 Server

Communication

• DNP3.0 Level 3 Serial (Slave)- with secure authentication implemented • DNP3.0 over TCP/IP (Slave) with secure authentication implemented. • IEC 61850 Server

Power Input

• Direct Power Input: 24 VDC, 10watts

Status Input

• 24 Digital Inputs • Interface: Dry contacts; 24VDC wetting voltage • SOE Time Stamp Resolution: 1msec • Contact de-bounce time periods are configurable. • Input circuits are optically isolated from external signal

Control Outputs

• Select Check Before Operate (SCBO) and Direct Operate • Select time and Operate time: configurable • Number of Outputs: 6 relays • Contact Arrangement: 1 Form A (SPST) • Contact Rating: 16amps@24VDC; 16amps@250Vac

AC Analog Inputs

• Acquire analog input directly without transducers from each of the 3-phase power system voltage and current • Use voltage and current input for calculations: i) Line-to-line voltage input ii) Phase current magnitude and phase angles iii) Real and Reactive power (3phase kW and kVar totals with sign) iv) Power factor • Accepts AC input voltage signals with a normal input level of 110V • Employ analog to digital converter with minimum of 16-bit resolution for a bipolar input signal • Accurately resolve ac voltage input signal levels from 0 to 150V • Accurately resolve ac current input signals with normal ranges of 0 to 1A or 0 to 5A. • Capable to report all analog values that have changed by more than their programmable dead bands from the last values • Record maximum rms fault current signals, over a period of at least one(1) second, up to 20 times normal (60A) within a maximum error of 2.5% of Full Scale Deflection (FSD) • Sampling rate for ac quantities < 64 samples per cycle

Time and Date Module

• Time resolution of internal clock: (1) msec without time synchronization, time drift is not more than 5msec per hour • Able to receive DNP3.0 compliant time and date message that contain Greenwich Mean Time (GMT) reference signal • Able to synchronize the internal clock to the GMT time and date received from master

Web Server Module (Optional)

• Capable to upgrade and configure FTU firmware • Able to set FTU communication parameters • Able to set FTU clock and time, time synchronization, and fault detection features • Display and clearance of historical logs and the capability to export logs in CSV format • Simple MMI features • Able to do simulation of data point

1.2 Feeder Fault detection function

F80 can detect and distinguish three types of faults: over-current load, permanent fault and transient fault, the fault detection of these three types are controlled by the special network distribution program preset in the unit. Over-current load: when a line is overloaded but not severe enough to influence safe operation of the line, FTU-F80 will sense that the current excesses the preset “over-current start-up” value and send out an over-current remote signaling alarm. Transient fault: when transient fault occurs, F80 detects and judges according to the preset program that the circuit breaker (C.B) in the substation trips, and after the circuit breaker has successfully reclosed once or several times, the system will clear the fault and resume power supply. The FTU-F80 sends out two kinds of alarm signal: over-current remote signaling and C.B action signaling alarm. Permanent fault: when permanent fault occurs, 80 detects and judges according to the preset program that the circuit breaker in the substation trips, and in case of the circuit breaker failed to reclose once or several times , the circuit breaker will be locked in its tripping mode and the fault cleared off. At this time FTU-F80 sends out three kinds of alarm signals: over-current remote signaling, breaker action and breaker locking. The following are the Protection Function build into the FTU: • Overcurrent (ANSI 50/51, 50G/51G) • Sensitive earth fault (ANSI 50SEF) • Directional relay (ANSI 67) • Broken Conductor (ANSI 46BC) • Negative sequence voltage (ANSI 47) The FTU is able to report fault event, fault direction and fault clearance event details as time-stamped sequence of events (SOEs). It is also able to save 128 fault events along with corresponding fault direction and associated fault clearance event details upon demand and report to the master.

The FTU support a configurable format for local record reporting including the Comma Separated Variable (CSV) format for use in a spreadsheet and the COMTRADE (IEEE C37.111-1999) format for use with a commercial COMTRADE viewer.

2. Hardware Architecture and working principle

2.1 Dimension & interface of the FTU-F80

Dimension of the FTU-F80 unit is 240 x 375 x 62mm .

2.2 Terminal Connection of FTU-F80

Document image


2.2.1 JPW: Power Interface

The connector JPW is describe in Table 1.

Terminal

Terminal No.

Abbreviation

Meaning

JPW

1

SYP+

+24VDC Power



2

SYP-

-24VDC Power

Table 1: Description of connector “JPW”

2.2.2 JVT1, JCT1 & JCT2: AC Voltage and Current Interface

The connector JVT1, JCT1 & JCT2 is describe in Table 2.

Terminal

Terminal no.

Abbreviation

Meaning

Measurement type

JVT1

1

V0

Line A

AC Voltage 110V



2

V0*

Line A Neutral

AC Voltage 110V



3

V1

Line B

AC Voltage 110V



4

V1*

Line B Neutral

AC Voltage 110V



5

V2

Line C

AC Voltage 110V



6

V2*

Line C Neutral

AC Voltage 110V

JCT1

1

I0

Line A

AC Current 1A or 5A



2

I0*

Line A Neutral

AC Current 1A or 5A



3

I1

Line B

AC Current 1A or 5A



4

I1*

Line B Neutral

AC Current 1A or 5A



5

I2

Line C

AC Current 1A or 5A



6

I2*

Line C Neutral

AC Current 1A or 5A

JCT2

1

I3

Line A

AC Current 1A or 5A



2

I3*

Line A Neutral

AC Current 1A or 5A



3

I4

Line B

AC Current 1A or 5A



4

I4*

Line B Neutral

AC Current 1A or 5A



5

I5

Line C

AC Current 1A or 5A



6

I5*

Line C Neutral

AC Current 1A or 5A

Table 2: Description of connector “JVT1, JCT1 & JCT2”

2.2.3 JDI: DI Interface

The connector JDI1, JDI2 & JDI3 is describe in Table 3.

Terminal

Terminal no.

Abbreviation

Meaning

Measurement type

JDI1

1

L0

DI0

+24Vdc Digital Input



2

L1

DI1

+24Vdc Digital Input



3

L2

DI2

+24Vdc Digital Input



4

L3

DI3

+24Vdc Digital Input



5

L4

DI4

+24Vdc Digital Input



6

L5

DI5

+24Vdc Digital Input



7

L6

DI6

+24Vdc Digital Input



8

L7

DI7

+24Vdc Digital Input

JDI2

1

L8

DI8

+24Vdc Digital Input



2

L9

DI9

+24Vdc Digital Input



3

L10

DI10

+24Vdc Digital Input



4

L11

DI11

+24Vdc Digital Input



5

L12

DI12

+24Vdc Digital Input



6

L13

DI13

+24Vdc Digital Input



7

L14

DI14

+24Vdc Digital Input



8

L15

DI15

+24Vdc Digital Input

JDI2

1

L16

DI16

+24Vdc Digital Input



2

L17

DI17

+24Vdc Digital Input



3

L18

DI18

+24Vdc Digital Input



4

L19

DI19

+24Vdc Digital Input



5

L20

DI20

+24Vdc Digital Input



6

L21

DI21

+24Vdc Digital Input



7

L22

DI22

+24Vdc Digital Input



8

L23

DI23

+24Vdc Digital Input

Table 3: Description of connector “JDI1, JDI2 & JDI3”

2.2.4 JDO1, JDO2, JDO3 & JDO4: DO Interface

The connector JDO1 & JDO2 is describe in Table 4.

Terminal

Terminal no.

Abbreviation

Meaning

Measurement type

JDO1

1

T0

DO0 Open

+24Vdc Digital Output



2

T0*

DO0 Open Common

+24Vdc Digital Output



3

C0

DO0 Close

+24Vdc Digital Output



4

C0*

DO0 Close Common

+24Vdc Digital Output

JDO2

1

T1

DO1 Open

+24Vdc Digital Output



2

T1*

DO1 OpenCommon

+24Vdc Digital Output



3

C1

DO1 Close

+24Vdc Digital Output



4

C1*

DO1 Close Common

+24Vdc Digital Output

JDO3

1

T2

DO2 Open

+24Vdc Digital Output



2

T2*

DO2 OpenCommon

+24Vdc Digital Output



3

C2

DO2 Close

+24Vdc Digital Output



4

C2*

DO2 Close Common

+24Vdc Digital Output

JDO4

1

T3

DO3 Open

+24Vdc Digital Output



2

T3*

DO3 OpenCommon

+24Vdc Digital Output



3

C3

DO3 Close

+24Vdc Digital Output



4

C3*

DO3 Close Common

+24Vdc Digital Output

Table 4: Definition of connecting terminal JDO1, JDO2, JDO3 & JDO4

2.2.5 JLR Interface

The connector JLR is describe in Table 5.

Terminal

Terminal no.

Abbreviation

Meaning

JRL

1

RL

Remote/Local



2

RL*

Remote/Local Common

Table 5: Description of connector “JRL”

2.3 Communication Module of the Feeder Device Control Unit

2.3.1 Communication Interface of JCOM Port (RS232/RS485)

Document image




The communication port JCOMs is describe in Table 6.

Pins

1

2

3

4

5

6

7

8

9

JCOM0

485 (-)

485 (+)

N.A.

N.A.

GND

N.A.

N.A.

N.A.

N.A.

JCOM1

DCD

RX

TX

N.A.

GND

N.A.

RTS

CTS

N.A.

2.3.2 DIP Switch settings of the FTU

The FTU-F80’s DIP switch is set as per customer requirements for the proper operation. The meaning is described in Table 7. The “OFF” position mean “1” and the “ON” position mean “0”.

SW

1

2

3

4

S0

ON: COM0 (Maintenance Mode)

ON: COM1 (Maintenance Mode)

x

x



OFF: COM0 (Normal Operation)

OFF: COM1 (Normal Operation)

x

x

Note

Maintenance Mode: Protocol set is PA-FTU, baud rate: 9600bps, 8,N,1

SW

Bit No.

Abbreviation

Meaning

S1

1

ON

RS 485 – Matching Resistance On (120Ω)



2

ON

RS 485 Pull Up Bias Resistance On



3

ON

RS 485 Pull Down Bias Resistance On



4

N.A.



SW

1

2

3

4

Remarks

S2

ON

ON

OFF

OFF

COM 0 – RS232



OFF

OFF

ON

ON

COM 0 –RS485

Table 7: DIP switch “S1, S2 & S3” settings

2.3.3 Ethernet Interface of the FTU

FTU-F80 comes with 2 Lan ports (RJ45).

Pin2

1

2

3

4

5

6

7

8

JLAN0

TX1 (+)

TX1 (-)

RX1 (+)

N.A.

N.A.

RX1 (-)

N.A.

N.A.

JLAN1

TX2 (+)

TX2 (-)

RX2 (+)

N.A.

N.A.

RX2 (-)

N.A.

N.A.

Table 8: Description of JLAN Ports

2.3.4 LED indication & System Status of the FTU-F80

The FTU-F80 has 15 LED indication to display the working status of the unit.

Figure 4: Description of the System LED Indication of the FTU-F80
Figure 4: Description of the System LED Indication of the FTU-F80


The system LED indication is described in Table 9.

Color

Abbreviation

Meaning

Status

Red

PW1

Power to Unit

Permanent

Red

PW2

Power to Unit

Permanent

Red

PW3

Power to Unit

Permanent

Red

RX1

COM1 Receive

Flashing

Green

TX1

COM1 Transmit

Flashing

Red

RX0

COM0 Receive

Flashing

Green

TX0

COM0 Receive

Flashing

Red

LAN1

LAN1 Status

Permanent

Green

LNK1

LAN1 Rx/Tx

Flashing

Red

LAN0

LAN0 Status

Permanent

Green

LNK0

LAN0 Rx/Tx

Flashing

Red

D0

Remote Control

Flash Once

Red

DI

Digital Input

Flash Once

Green

RUN

In operation

Flashing

Red

FLT

Fault

Permanent

Table 9: System LED status of FTU-F80

2.3.5 Digital Input & Command Output LED status of the FTU-F80

The FTU-F80 have 24 LED indication to display the digital input status of the unit.

Fig 5: Description of the Digital Indication LED status of the FTU-F80
Fig 5: Description of the Digital Indication LED status of the FTU-F80


The digital indication LED status is described in Table 10.

JDIs

Abbreviation

Color

Meaning

JDI1

L0

Red

DI0 Input



L1

Red

DI1 Input



L2

Red

DI2 Input



L3

Red

DI3 Input



L4

Red

DI4 Input



L5

Red

DI5 Input



L6

Red

DI6 Input



L7

Red

DI7 Input

JDI2

L8

Red

DI8 Input



L9

Red

DI9 Input



L10

Red

DI10 Input



L11

Red

DI11 Input



L12

Red

DI12 Input



L13

Red

DI13 Input



L14

Red

DI14 Input



L15

Red

DI15 Input

JDI3

L16

Red

DI16 Input



L17

Red

DI17 Input



L18

Red

DI18 Input



L19

Red

DI19 Input



L20

Red

DI20 Input



L21

Red

DI21 Input



L22

Red

DI22 Input



L23

Red

DI23 Input

Table 10: Digital Input LED status of FTU-F80

The FTU-F80 have LED indication to indicate the command execution of the unit.

Fig 6: Description of the Digital Input & Command Output LED Indication
Fig 6: Description of the Digital Input & Command Output LED Indication


3. Basic Measurement Module

For the externally input voltage and current signals, the system makes 64 points of sampling every cycle; the A/D conversion accuracy of each point is 16-bit. Sampling speed is adjusted to match the frequency change of the measured signals. Calculations on the sampling point is in the digital signal processor (DSP). The calculated values in the buffer zone of the data is access by the data acquisition and information monitoring data communication protocol as well as other application software of the FTU-F80 Feeder terminal unit. Calculated values of the software are as below.

Calculated value

Unit

Scale

Description

Phase voltage

V, effective value

Configurable

Phase A, B, and C: For each group of input of the three voltages, the Y connection measures the three-phase voltage, while Δ connection cannot calculate the three-phase voltage.

Line voltage

V, effective value

Configurable

AB, BC, and CA: For each group of input of the three voltages, the Y connection calculates the three line voltages, while Δ connection measures the three line voltages.

Current

A, effective value

Configurable

For the three current inputs of each group, Phase A, B, C and zero sequence current.

Active power

Watt, effective value

Configurable

Phase A, B and C voltages are terminate out from voltage terminal. Phase A, B and C currents are terminate out from current terminal. If there exists the second group of input current, voltage terminal may be set as common terminal.

Reactive power

Var, effective value

Configurable

Phase A, B and C voltages are terminate out from voltage terminal, and Phase A, B and C currents are terminate out from current terminal. If there exists the second group of input current, voltage terminal may be set as common terminal.

Apparent power

VA, effective value

Configurable

Phase A, B and C voltages are terminate out from voltage terminal, and Phase A, B and C currents are led out from current terminal. If there exists the second group of input current, voltage terminal may be set as common terminal.

Active kilowatt-hour

KWH, effective value

Configurable

Calculates active kilowatt-hour.

Reactive kilowatt-hour

KVH, effective value

Configurable

Calculates reactive kilowatt-hour.

Power factor



Configurable

Phase A, B and C voltages led out from voltage ter-minal and Phase A, B and C currents. If there exists the second group of input current, voltage terminal may be set as common terminal.

Phase angle

Degree

900 corresponds to 90 degrees

Phase angle difference between Phase A, B and C voltages led out from voltage terminal and Phase A, B and C currents. If there exists the second group of input current, voltage terminal may be set as common terminal.

Frequency

Hz

900 corresponds to 90 degrees

Frequency of current or voltage led out from the first or third group of terminals.

4. Maintenance Software for FTU-F80

The maintenance software functions as parameter configuration of, real-time data display, sending remote control command, uploading, and downloading of parameter files, etc.

4.1 Main Interface

The main interface is as follow:

Document image


4.2 Tool Bar

The icon as in the tool bar are describe as follows.

Document image


4.3 Status Bar

The status bar indicates the current state the between the laptop and the FTU:

Document image


Parameter

Description

Mode



- Local

Direct Connect to the FTU.

- Remote

Connect via the network to FTU.

Address

0 - 65535

State



- Open

No connection to FTU.

- Close

Connected to FTU.

Setting



- IP Connection

Information for TCP connection.

- Serial Connection

Information for serial connection.

4.4 Communication

4.4.1 Communication Setting

The communication to the FTU can be via Serial or Ethernet port connection.

Document image


4.4.1.1 Serial Setting

The serial port is configured as below:

Document image


Parameter

Description

Example

Unit

COM

COM1 - COM64

COM1



Baud Rate

300, 600, 1200, 2400, 4800, 9600, 14400, 19200, 38400

9600



Data Bits

5, 6, 7, 8

8



Stop Bits

1, 1.5, 2

1



Parity

None, Odd, Even

None



4.4.1.2 Net Setting

The Net Setting is configured as below:

Document image


Parameter

Description

Example

Unit

FTU IP

IP Address as configured in FTU.

192.168.1.11



Local IP

IP Address of laptop or computer. It can be configured 0.0.0.0 for not care about the computer's IP address.

192.168.1.10



Port

TCP Port.

2405



4.4.2 Port Open

To open the connection to FTU.

Step 1: Click on Open Port or the icon as below.

Document image


Step 2: Open Port and icon will be grayed out and state will show “Open”

Document image


4.4.3 Port Close

To close the connection to FTU.

Step 1: Click on Close Port or the icon as below.

Document image


Step 2: Close Port will grayed out and state will show “Close”.

Document image


4.4.4 Address

The default maintenance address as set in FTU is 0. The global address is set to 65535 if the address set in FTU is unknown.

4.4.4.1 Direct connect to FTU

Step 1: Click on Address or the icon as below.

Document image


Step 2: Set the FTU Address as configured in FTU. Select Local for direct connection to FTU and click Ok.

Document image


4.4.4.2 Connect the FTU remotely through the communication network

Step 1: Click on Address or the icon as below.

Document image


Step 2: Set the FTU Address as configured in FTU. Select Remote for connecting FTU via the network and click Ok.

Document image


Step 4: Click on Switch to Maintenace Mode.

Document image


Step 5: Click on Select then Switch, now it is operating in the maintenance mode on the communication port.

Document image


4.5 Setting Parameter

The Setting Para is to configure the IO points and function of the FTU.

Document image


4.5.1 Upload

The setting of the FTU is upload upon issue of this command. The configuration of FTU will be uploaded from FTU to the F80 maintenance software.

Step 1: Click on Upload or the icon as below.

Document image


Step 2: A pop-up window will indicate whether the command is successful.

Document image


4.5.2 System

Step 1: Click on System or the icon as below.

Document image


Step 2: A pop-up window will indicate whether the command is successful.

Document image


Parameter

Description

Example

Unit

AI Module Type

100V/1A or 100V/5A

100V/5A



Frequency

50Hz or 60Hz

50Hz



DIDO Card0

Connect/Disconnect

Connect



DIDO Card1

Connect/Disconnect

Connect



AI Card

Connect/Disconnect

Disconnect



Current Suppress(A)

Secondary current for current suppression

0

A

Voltage Suppress(V)

Secondary voltage for voltage suppression

1

V

Fragment Size

A number in byte for sending in each fragment message.

128



DDI Interval(ms)

Double digital input** **

5000

ms

FREQ Full

Frequency full scale

100



FREQ Scale

Frequency engineering scale

10000



FRE Deadband

Frequency deadband

100



MAX_SOE

A number of maximum SOEs in FTU buffer.

512



4.5.3 AI

Step 1: Click on AI or the icon as below.

Document image


Step 2: Configure AI parameters.

Document image


Setting same to every node

To set the parameter to every node.

Feeder of Node

Number of feeders of the node defines number of feeder loops formed by the input voltage and current of the node unit.

Type

0-Other, 1-Star, 2-Delta, 3-null.

Va/Vab, Vb/Vbc, Vc/Vcb & Ia, Ib, Ic

The connecting terminal on the FTU correspond to the channel number 0~14. For example, the voltage Va of the first power line indicates the voltage at phase A that is define as 0, refers to the signal connecting the first circuit (VT) of the connection board. The current Ia indicates the current at phase A that is define as 6, refers to the signal connecting to the seventh circuit (CT) of the connection board. A Null indicates that there is no signal connected to the terminal. The software configure as Va/Vab, Vb/Vca and Vc/Vcb. The define voltages will display as [Va, Vb, Vc] or [Vab, Vca, Vcb] as per the connection method of star or delta. If non-star or non-delta connection method is select, the voltage input will display as the phase angle of the phase voltage without calculating the power. i.e. Only measurements are available. As for delta connection, 3 connection modes are provided so as to correctively calculate the total power of the power lines and the corresponding equation: P = Vab*Ia + Vcb*Ic = Vba*Ib + Vca*Ic = Vac*Ia + Vbc*Ib, of which the relationship must strictly follow to correspond the input/output of the voltage during connection. When defining, whether interface Vab represents Vab or Vba, interface Vca represents Vca or Vac and interface Vcb represents Vcb or Vbc will determine by the physical connection. From the point of view, voltage |Uab|=|Uba|, |Uca|=|Uac| and |Ucb|=|Ubc| must be determine during connection to calculate power.

Balanced

3-phase balance defines whether the 3-phase voltage and current in the loop are balanced. Normally this is configured as False (unbalanced).

Step 3: Setting of scaling parameter.

Click on NO. 0, a pop up menu UI parameter appears. This is to set the scaling and deadband of the voltage, current, kW, kVar and power factor of the power line.

Document image




Parameter

Description

Example

Unit

U Set







- PriFull(KV)

Full scale primary voltage.

30

kV

- SecFull(V)

Full scale secondary voltage.

150

V

- Scale

Full scale engineering voltage.

3000



- DeadBand

Deadband for sending to the Master which is described in engineering value.

30



I Set







- PriFull(A)

Full scale primary current.

600

A

- SecFull(A)

Full scale secondary current.

1

A

- Scale

Full scale engineering current.

600



- DeadBand

Deadband for sending to the Master which is described in engineering value.

6



PQ Set







- PriFull(MW)

Full scale primary power.

31.17

MW

- SecFull(W)

Full scale secondary power.

259.8

W

- Scale

Full scale engineering power.

3117

(31.17*100)

- DeadBand

Deadband for sending to the Master which is described in engineering value.

31



PF Set







- PriFull

Full scale primary power factor.

1



- SecFull

Full scale secondary power factor.

1



- Scale

Full scale engineering power factor.

10000



- DeadBand

Deadband for sending to the Master which is described in engineering value.

100



Note: PEA Deadband

Voltage = +/- 5 % Current = +/- 1 %

4.5.4 DI

The DI setting is to set the debouncing time for the physical DI.

Step 1: Click on DI or the icon as below.

Document image


Step 2: A pop-up window will indicate whether the command is successful.

Document image


Parameter

Description

Example

Unit

NO.

Physical Digital Input

0



Type

SOE, DI, PI

SOE



Rev

false, true

false



Delay

Debouncing time in DI.

14

ms

4.5.5 DDI

This dialogue box is used to set Double Contact, 2-State status (DC-2S) parameters.

Step 1: Click on DDI or the icon as below.

Document image


Step 2: A pop-up window will indicate whether the command is successful.

Document image


Parameter

Description

Example

Unit

NO.

DDI Number

0



DI Off

Double digital input Off state

7



DI On

Double digital input On state

9



Note

The number is Send Table numbers of DI.

4.5.6 DO

Step 1: Click on DO or the icon as below.

Document image


Step 2: Configure DO parameters.

Document image


Parameters

Description

Example

Unit

NO.

DO number

0



Type

DO, SBO, LRR_DO, LRR_SBO, SOFT_DO, SOFT_SBO

SBO



Pulse Duation(.01s)

This is the holding time when relay close/trip. Unit of time is in 10 msec. If the checkbox is tick, it will take the setting of FTU. Else it will follow the master setting.

100

0.01 s

Select Timeout(s)

This is the timeout limit for Select before operate. The FTU receive a select command, if the execution is not receive within the ‘Select’ time limit as set, the control is cancel. Unit of time is in second.

20

s

Step 3: Setting of command interlocking logic. Left click on the Interlock, a pop-up menu DO Lock appears. This is to set the interlocking logic as per requirement.

Document image


Parameters

Description

Example

Unit

Status

Close/Open status.





- Neutral

Must be a signal of Open status.

9



- Not gate

Must be a signal of Close status.

8



Local/Remote

Local/Remote status.





- Neutral

Must be a signal of Remote status.

6



- Not gate

Must be a signal of Local status.

7



Lock 1

Other interlock 1.





- Neutral

Optional signal.

255



- Not gate

Optional signal.

19



Lock 2

Other interlock 2.





- Neutral

Optional signal.

17



- Not gate

Optional signal.

18



Note

The number is Send Table numbers of DI.

Step 4: Setting of AC Synchronous logic (For information only). Left click on the setting, a pop up menu Synchronous Setting appears. This is the set the condition to compare the voltage and phase angle between 2 feeders before a close command is execute.

Document image


Parameter

Description

Example

Unit

DO Selection

DO Number.

0



Condition







- Diff Voltage(V)

Voltage difference between feeder A and B.

25

V

- Diff Phase(D)

Phase Angle difference between feeder A and B.

10.01

D

- Min Voltage(V)

Minimum voltage in Feeders to consider above conditions.

10

V

DI No. (Switch Status)







- Close

DI point assigns to status close. [if not assigning, set to 255]

255



- Trip

DI point assigns to status open. [if not assigning, set to 255]

255



Feeder No. (Base A)

Setting of which feeder.

0



Feeder No. (Base B)

Setting of which feeder.

1



DO Close Operation

If ‘enable’, interlocking need to be check before close operation.

Disable



DO No. (Synchronous Indication)

If select, and DO number choose, close command is execute for AC change from sync to unsync. Open command is execute for AC change from unsync to sync.

5



4.5.7 Protection

Document image


4.5.7.1 Feeder Fault Current Detection

Step 1: Click on Protection or the icon and set the parameter.

Document image


Parameter

Description

Example

Unit

(1) Over Current

Current value for starting "Feeder Fault Detection" (Pickup Current)

1

A

(36) Return of V

Voltage value for "Return to normal" (Drop-off Voltage)

50

V

(50) Lost of V

Voltage value for starting "Feeder Fault Detection" (Pickup Voltage)

40

V

(23) Return of I

Current value for "Return to normal" (Drop-off Current)

0.01

A

(35) Return Type

"0" : check both voltage and current for Feeder Fault Detection. "1" : check only current for Feeder Fault Detection.

0

0:V;1:A;

(29) 1st Reclose

Reclosing period for 1st Feeder Fault Detection.

500

ms

(30) 2nd Reclose

Reclosing period for 2nd Feeder Fault Detection.

15000

ms

(21) Reclaim

Time for "Return to normal". It must be more than "1st Reclose" + "2nd Reclose"

20000

ms

Step 2: Click on Platen and change Quick Break Alarm to "ON".

Document image


4.5.7.2 Overcurrent Fault (ANSI 50/51, 50G/51G)

Step 1: Click on Protection or the icon and set the parameter.

Document image


Parameter

Description

Example

Unit

(1) Over Current

Pickup current for IDMT Curve.

1

A

(3) PH DMUL

Pickup multiply for DT Curve. DT pickup current is equal to (5) DT MUL * (1) Over Current

2



(4) Qualify OC

Definite time delay.

22

0.01 s

(2) PH uiTf

IDMT time multiplier.

100

0.01 s

(5) PH DTIns MUL

Pickup multiply for Instantaneous Curve. Instantaneous pickup current is equal to (18) DT Ins MUL * (1) Over Current

3



Step 2: Click on Platen and change Quick Break Alarm to "ON" and I Protection to "ON".

Document image


Step 3: Click on Curve Setting and choose an inverse curve.

Document image

An axample for Overcurrent curve
An axample for Overcurrent curve


4.5.7.3 Sensitive Earth Fault (ANSI 50SEF)

Step 1: Click on Protection or the icon and set the parameter.

Document image


Parameter

Description

Example

Unit

(9) Gr DTMUL

Pickup multiply for DT Curve. DT pickup current is equal to (9) DT MUL * (7) Neutral OC

2



(7) Neutral OC

Pickup current for IDMT Curve.

0.5

A

(8) Gr uiTf

Instantaneous time multiplier.

100

0.01 s

(11) Gr DTIns MUL

Pickup multiply for Instantaneous Curve. Instantaneous pickup current is equal to (11t) DT Ins MUL * (7) Neutral OC

3



(10) Qualify Neutral

Definite time delay.

22

0.01 s

Step 2: Click on Platen and change Neutral Alarm to "ON" and Neutral Protection to "ON".

Document image


Step 3: Click on Curve Setting and choose an inverse curve.

Document image

An axample for Sensitive Earth Fault curve
An axample for Sensitive Earth Fault curve


4.5.7.4 Directional relay (ANSI 67)

Step 1: Click on Protection or the icon and set the parameter.

Document image




Parameter

Description

Example

Unit

(13) Torque Angle

Pickup angle.

60

deg

(14) Angle Reserve

"1": Reverse Directional Relay "0": Forward Directional Relay

0



Step 2: Click on Platen and change Pow Dir Alarm to "ON".

Document image

An axample for Directional Relay curve
An axample for Directional Relay curve


4.5.7.5 Broken Conductor (Phase-Sequence or Phase Balance Voltage Relay: ANSI 47)

Step 1: Click on Protection or the Icon and set the parameter which will have the logic as shown in the picture below.

Document image


Parameter

Description

Example

Unit

(39) Broken LVolt

Voltage Drop-off

60

V

(40) Qualify Broken

Voltage pickup

100

x0.01s

Logic for PT Broken Conductor
Logic for PT Broken Conductor


Step 2: Click on Platen and change PT Broken to "ON".

Document image


4.5.7.6 Broken Conductor (Reverse-Phase or Phase Balance Current Relay: ANSI 46)

Step 1: Click on Protection or the Icon and set the parameter.

Document image




Parameter

Description

Example

Unit

(41) I2/I1 Rate

Pickup. negative sequence current / positive sequence current

0.3



(40) Qualify Broken

Definite time delay.

100

0.01 s

Step 2: Click on Platen and change CT Broken to "ON".

Document image


4.5.7.7 Analog value: Fault Current (Sag Swell)

Step 1: Click on Protection or the Icon and set the parameter.

Document image




Parameter

Description

Example

Unit

(16) FC Starts

Pickup for Fault Secondary Current. It should be configured as same as (1) Over Current

1

A

(17) FC Full

Maximum Fault Secondary Current.

20

A

(18) FC Full Scale

Maximum enginnering value for reporting to SCADA.

12000

(600A * 20times)

(19) FC DeadBand

Deadband of engineering value for reporting to SCADA.

10



(22) End Fault Dis

0: Hold Fault current value at peak value. 1: Not hold Fault current value at peak value and return to zero. 2.Hold Fault current value at peak value and return to zero when Feeder Fault Current return to normal

0



(20) I Qualify(min)

Minimum time for starting capture Fault current.

10

0.01 s

(21) I Qualify(max)

Maximum time for ending capture Fault current.

20000

0.01 s

4.5.8 AVR

Document image

Document image


A. Linear Curve

B. Intregrate Curve

To design for the adjustable of the tap position of regulator by considering the following parameters:- Volage set point : - 95 ~130Vac- Time delay: 10 ~ 180 sec - Bandwidth: ±0.6% to ±6%

To design for adjustable of the tap position of regulator by formula: (∆U ı%ı) / E ı±%ı - (∆U = % of Voltage differential of Load Voltage - E = ± of bandwidth in % unit.

A. Linear curve: able to control adjust the Tap position of Regulator will be depend of the condition follow these parame-ter: i) Voltage Set point is the voltage level to compare with voltage from PT that RTU read (actual Voltage). It mean that if the actual value is different with the Voltage Level of RTU, it will sent Raise/Lower Command to control the Tap Position of Regulator. The FTU is able to readjust the Voltage Set point between 95-130 Vac by receiving the AO command from master. In case of power loss, FTU will still be able to remember last Voltage set point. ii) Time Delay is the setting time for delay consider the Actual Voltage in case of Actual value not same with voltage level, RTU have to count time during the Actual Voltage difference with Voltage Level. If the voltage has been difference until equal with time setting then RTU will send Raise/Lower command to adjust the Tap position of Regulator. Contractor have to designed for RTU able to change value to Time delay in unit of Second between 10-180 Sec. and RTU shall able to mem-orize last count of Time Delay.(incase RTU lost of DC Supply). iii) Bandwidth = Width of changing Voltage Level (in unit of %) that RTU will not send the control command to Raise/Lower Tap Position of Regulator, ie. Bandwidth = 1% of Voltage level at 110Vac then the bandwidth will be between 108.9 Vac. to 111.1 Vac. Contractor shall designed the RTU to able to adjust the Bandwidth setting value between ± 0.6 until ± 6 % of Voltage Level and RTU shall able to memorize the last setting Bandwidth (in case of RTU lost of DC supply). B. Integrate curve: Characteristic of adjust Tap position of Regulator shall be follow formula in Table 1 only. And will not consider the condition of Linear Curve because in some distribution line, the Voltage level will not stable and some time will higher and lower in the short time then it not able to apply the linear curve in to these condition. If apply the Linear curve in unstable line, it will make the electric user get damaged from this condition. The Integrate curve will work by adjust the Tap position of Regulator until the Voltage level change to the normal with no Time delay.

4.5.9 SCB CFG

Document image


4.5.10 PLC CFG

Step1: Configure PLC setting.

Document image


Parameter

Description

Example

Unit

INPUT0

0 - 127 and NULL

65



INPUT1

0 - 127 and NULL

68



INPUT2

0 - 127 and NULL

71



INPUT3

0 - 127 and NULL

93



Logic Gate

OR, AND, XOR

OR



Note

The number is Send Table numbers of DI.

Step2: Add point "Inter 215" PLC0 CFG to Send Table.

Document image


4.5.11 ATS

Document image


4.5.12 Encryption

Document image


4.5.13 Channel

Document image


Parameter

Description

Example

Port Settings





- Protocol

DNP3.0, IEC101 and so on.

DNP3.0

- Bandrate

300, 600, 1200, 2400, 4800, 9600, 14400, 19200, 38400

9600

- Data Bits

5, 6, 7, 8

8

- Parity

None, Odd, Even

None

- Stop Bits

1, 2

1

- Flow Control

RTS Mode, None

RTS Mode if use Dataradio(Analog Radio) // None if use Hauwei(Digital Radio)

- DCD Hold

None, Raised, Dropped

None, 0

- RTS Hold

None, Raised, Dropped

Dropped, 15

- RTS/CTS

None, check Raised, check Dropped

check Raised 10

Protocol Settings





- AI Send No.

Number of AI sent to master

16

- DI Send No.

Number of DI sent to master

30

- PI Send No.

Number of PI sent to master

0

- FTU Address

Protocol Address for the FTU

2

- Master Address

Protocol Address for the Master (SCADA)

1

- Unsolicited

Enable, Disable

Enable

- DMS Time

GMT-12, GMT-11, GMT-10, ..., GMT, ..., GMT+10, GMT+11, GMT+12

GMT

- FTU Time

GMT-12, GMT-11, GMT-10, ..., GMT, ..., GMT+10, GMT+11, GMT+12

GMT+7

- Request Time (min)

Request time synchronization from master

480

- Resend Interval (ms)

Resend period for an unconfirmed message. For instance, in unsolicited mode, when communication is loss, FTU will resend data within the defined time.

1000

- Comm Lost (s)

When there is no data transmission during the configured period, the communciation lost flag is raised.

300

- Delay Time (s)

Delay time for sending messages.

0

- Resend Num

Resend number for an unconfirmed message.

3

4.5.14 Net

Document image


Parameter

Description

Example

Protocol

DNP_NET, IEC104 and so on.

DNP_NET

Send Count





- AI

Number of AI sent to master

16

- DI

Number of DI sent to master

30

- PI

Number of PI sent to master

0

FTU IP

IP Address of FTU

192.168.1.11

Mask

Subnet mask of FTU

255.255.255.0

Port

Port for the protocol

20000

Master IP

SCADA IP address

0.0.0.0

Gateway

Default Gateway of FTU

192.168.1.1

Mode

Server, Client

Server

Type

0-UDP, 1-TCP

1-TCP

Link

0-No, 1-Yes (Not Use)

N/A

Relink

Not Use

N/A

T1 time

t1 specifies that after the sender sends an I-format message or U-format message, it must be approved by the receiver within the time of t1, otherwise the sender thinks that there is a problem with the TCP connection and should re-establish the connection

15

T2 time

t2 stipulates that after receiving the I format message, if the receiver does not receive a new I format message after t2 time, it must send the I format message that the S format frame has received to the sender for approval. Must be less than t1.

10

T3 time

t3 stipulates that the scheduling end or the RTU end of the substation will trigger the timer t3 every time it receives an I frame, S frame or U frame. If no message is received within t3, it will send a test link frame TESTFR to the other party.

20

Send Win

IEC104 Send Window

1

Recv Win

IEC104 Receive Window

1

FTU Address

Protocol Address for the FTU

2

Master Address

Protocol Address for the Master (SCADA)

1

Unsolicited

Enable, Disable

Enable

DMS Time

GMT-12, GMT-11, GMT-10, ..., GMT, ..., GMT+10, GMT+11, GMT+12

GMT

FTU Time

GMT-12, GMT-11, GMT-10, ..., GMT, ..., GMT+10, GMT+11, GMT+12

GMT+7

Request Time (min)

Request time synchronization from master

480

Reply Timeout (10ms)

In unsolicited mode, in the event communication is loss, time to resent the data.

1500

Comm Lost (s)

When no data transmission during the period set, communciation lost flag is raised.

180

4.5.15 61850 setting

Document image


4.5.16 Send Table

Configure Send Table for sending points to the Master.

Document image




4.5.17 Download

The setting of the FTU is download upon issue of this command. The configuration of FTU will be downloaded to FTU from the F80 maintenance software.

4.5.17.1 Download configuration to FTU partially.

Click on Down type(D) command and select which section that will be downloaded to FTU.

Document image


4.5.17.2 Download all configuration to FTU.

Click on Download command to download all configuration to FTU.

Document image

Parameters are downloading to FTU.
Parameters are downloading to FTU.


4.5.18 Write

After downloading configuration to FTU. User must using Write command to apply downloaded configuration.

Document image


4.4 Downloading of Parameters

The Download button in the classified configuration dialogue boxes and the options under the classified parameter-downloading menu are used to download parameters according to their kind. So, when certain kind of parameters is to be changed, only that kind of parameters can be downloaded. Among the kinds of parameters the node comprehensive parameters include node Feeder loop number parameter, and parameters defining whether to send harmonic or not, and whether to send integral kilowatt-hour or not. The node reference parameters include node positive and negative reference voltage parameter, temperature reference parameter. Node calibration parameters include AC phase compensation parameter, AC calibration factor parameter. Node remote metering parameters include Feeder loop definition parameter of that node.

4.4.1 Parameter files

The options under the parameter files menu are to be used for the save of parameters in the form of files, which include read access parameter, save parameter and parameter re-save.

4.4.2 Open command

Document image


Click the Open command option under the Para Files (F) tab, pop up the files open dialogue box and select file desination (extended file .dat). Press the open button, the maintenance software will update the data structure as per parameters in the file.

4.4.3 Save command

Click the Save command option under the Para Files (F) tab, and the maintenance software will save the currently parameters to the parameter file that has just been opened. If no parameter file has been read, then the default parameter file is ftu_para.dat.

4.4.4 Save as command

Document image


Click the Save As command option under the Para Files (F) tab, a Save As dia-logue box will pop up. Select name of file or enter new file name (extended file name is .dat), then click save, and the maintenance software will save the currently parameters to the parameter file.

5. On-Line Data & Diagnostics

On-line data is the data monitoring to monitor the real time data that is running in the FTU. By real time data the users can check system status, the real time value of the collected values, SOE items, fault report information, and real time transmitted and receipt data of the channel, etc.

5.1 Call data /Stop Data

Document image


A Call Data is to be activated if real time data of the FTU is to be monitored. A Stop Data command will deactivate the port to be monitored.

5.2 System status

The system status interface shows start-up status, status of the nodes, channel and the network.

Document image


Parameters

Description

Boot State



- Version

Boot State records the firmware version.

- Boot times

number of times the FTU is rebooted.

- Boot time

FTU last initialize time.

- FTU time

FTU current time.

Node State

Node State shows whether a certain node is normal or not, not installed or fails. Channel status.

Serial Channel State

Serial Channel State records receiving information bytes and error information bytes of the FTU.

Net Channel State

Net Channel State shows network card status, times of network overflow, times of network disconnection and errors. When the terminal has only 1 unit, the network card column shows no network card.

5.3 AO Data

This interface shows the AO data that are being written in the event the AO commands are sent from master to FTU.

Document image


5.4 AC

This interface displays all the real time AC measured values and actual values of one Feeder of a node, including frequency, three-phase current and voltage, zero sequence voltage and current, line voltage, three-phase active and reactive, apparent power, total active & reactive and apparent power, three-phase power factor and phase angle, total power factor and phase angle, active power integral kilowatt-hour, reactive integral watt-hour. If active and reactive integral watt-hour is to be viewed, the integral kilo-watt-hour option should first be selected in the remote metering parameter configuration dialogue box. The AC real time values of Feeders of other nodes can be viewed by select-ing node number and Feeder number of that node.

Document image


5.5 DI

Document image


5.6 SOE

Document image


This dialogue box shows the SOE item queue up to 1000 SOE items can be displayed. When the number of SOE items is less than 1000, the actual number will be displayed. When the number of SOE items is over 1000, the new SOE items will overwrite original ones. When the dialogue box is closed then opened again, all the item records will be cleared, and the system is ready to receive new SOE items. The displayed content includes node number that sends remote signaling deflection, channel number in the node, deflection feature of the remote signaling and remote signaling deflection transmission time.

5.7 History SOE

Document image


This interface shows the queue of the latest 512 SOE items. When the number of SOE items is less than 512, the actual number will be displayed. When new SOE items are generated after the interface has been opened, new records will not be added. New SOE items will be displayed only after the interface is closed and then re-opened.

5.8 Fault

Document image


This dialogue box shows whether a certain Feeder of a certain node works normally. If operation of the Feeder is normal, then no remote signaling report will appear in the fault status column, and the received value and processing value in the fault data list column will be zero. If fault occurs in that Feeder, the system will display fault termination time in the termination item of the fault report, and display causes of fault (phase over current, zero sequence over current, or zero sequence over voltage) and the circuitry status caused by the fault (circuit breaker action, breaker locks and grounding fault) in the fault status information column. In addition, the real time phase current and voltage values of one cycle before and after the fault of that Feeder will be displayed in the information column of fault data list. As shown in the picture, the over current start-up value of phase current is set at 6 A and overcurrent occurs in phase A, then the fault information generated under the condition of CB tripping is simulated.

5.9 Fault Current Events

Document image


This interface shows the queue of the latest 36 fault current items. When the number of fault current items is less than 36, the actual number will be displayed. When new fault current items are generated after the interface has been opened, new records will not be added. New fault current items will be displayed only after the interface is closed and then re-opened.

Parameter

Description

No

fault current serial number

Point

fault current sendtable serial number

Value

fault current value

Raw value

fault current raw value

Direct

fault current direction

P

the fault current active power

Q

the fault current reactive power

Change time

the fault current occurrented time

5.10 Fault Current History Events

Document image


This interface shows the queue of the latest 36 fault current items. When the number of fault current items is less than 36, the actual number will be displayed. When new fault current items are generated after the interface has been opened, new records will not be added. New fault current items will be displayed only after the interface is closed and then re-opened.

6 Command

Remote control operation can be conducted on FTU terminal equipment through maintenance software. There are two kinds of remote control which are single channel remote control and loop remote control.

Document image


6.1 DO Single

Document image


By selecting the remote control channel number and remote control closing or breaking, pressing the Send button, the system will issue a remote control select command to the FTU terminal equipment and then wait for check back result, with the process bar indicating the waiting time. If no feeedback is returned within 20 seconds, the system will display check back overtime. Under this condition, select to execute or cancel remote control and press the Send button, the system will issue execute or cancel remote control command to the FTU terminal equipment.

6.2 DO Cycle

Document image


Select the starting and ending channel numbers of remote control and then click the Start button, the system will execute loop remote control from the starting channel number to the ending channel number entered. New cycles automatically begin after the remote control has been conducted from the starting to the ending channel, and the system will exit loop control only after the Stop button is clicked. The execution process of the remote control channel is shown in the operation status box. Total times of remote control and times of faulty remote control will be displayed in the statistics box.

Warning!

Loop remote control will execute multi-channel remote closing and breaking, it should only be used for testing purposes when remote control line has not been connected to FTU or when all the remote control tie straps have been set out!!!

6.3 Adjust Time

Time calibration can set the system clock of the FTU terminal equipment, the value is configured according to the system clock value of the maintenance computer.

Document image


6.4 Reset FTU

This command will reset the FTU terminal unit and make it restart. Users can execute the Reset FTU command if wrong parameters have been downloaded but not to be saved. When this command is to be executed, first ensure that proper communication connection has been established and then the call data command can be used to confirm whether the resetting has successfully performed.

Document image


6.5 Clear Boot times

This command will reset the boot times record of the FTU to begin at 0.

Document image

Boot time have changed to 0.
Boot time have changed to 0.


6.6 Kill Process (Q-Process)

This command will reset the FTU as a watchdog features to kill the process of the FTU.

Document image


6.7 Erase History Data

This command will clear the SOEs Buffer stored in the FTU.

Document image


6.8 Init AO

This command allows the user to write the AO values in the FTU.

Document image


6.9 Simulation

This command allows the user to simulate DI and AI values in the FTU.

Document image


Parameter

Description

EN/DIS

EN = Enable point for simulation mode(checked)

DI

Check on the checkbox of DI and click SET to start simulation. To stop the simulation, click STOP.

AI

Fill the value on AI and click SET to start simulation. To stop the simulation, click STOP.

7 Monitor

The maintenance software can monitor the real time sending and receiving data information frames of each channel for the serial and LAN port. Click the Refresh button, current information can be cleared, and the system begins to receive new channel data. This provides great convenience for commissioning of the communication protocols.

Document image


8 Accessing Limiting password

Passwords are set for remote control, initialization and calibration of parameters, etc.

Document image


User

Level

Password

Access

PA

User level

FTU

1. Initialize parameters 2. Single channel remote control 3. Loop remote control

Adjust

System level

dms

1. Node parameter calibration 2. Command operation calibration 3. Classified downloading of reference and calbration

FTU

Development level

f80

1. All access

Note

The calibration users are only authorized for calibration and not authorized to conduct other operations, while the PA and F80 development group users are not authorized for calibration.

9 Fault Analysis & Troubleshooting

No

Issue

Cause

Measures

1

The unit number is not valid after being set.

The unit has not reset.

Press the reset button.

2

Incorrect channel remote control.

The remote control operation sequence number has not been set.

Set through maintenance PC.

3

There is no SOE information.

The remote signaling sending sequence number has not been set.

Set through maintenance PC.

4

The maintenance PC cannot open serial ports.

1. Serial port number incorrectly selected.2. Relative serial ports are used by other software.3. Relative serial ports damaged.

1. Select serial port number correctly. 2. Replace serial port or close other software 3. Replace serial port.

5

Communication between the unit and maintenance PC is abnormal.

1. The serial port is abnormal.2. The maintenance line connection is abnormal.3. Incorrect address setting.

1. Check the serial port.2. Replace connection cable or connect correctly.3. Set address correctly.

6

The four-color diamond rotates continuously during downloading and uploading and does not prompt finish information for a long time

1. Abnormal serial port or connection.2. Incorrect address setting.

1. Check serial port and connection.2. Set address correctly.

7

Incorrect remote control opera-ton.

1. Abnormal serial port or connection.2. .Incorrect address setting.3. Data are not called before remote control operation4. Incorrect remote control op-eration setting.

1. Check serial port and connection.2. Set address correctly.3. Operate after calling data.4. Set remote control parameters correctly.